With this kit, you’ll be ready to start your measurements in the commissioning, servicing and maintenance of refrigeration and air conditioning systems and heat pumps straight away: You will get the testo 550s smart digital manifold with Bluetooth and 2-way valve block, two fixed cable clamp temperature probes (NTC) and a robust transport case. Additional Bluetooth probes, e.g. for wireless measurements of temperature and vacuum, are available separately.
General technical data | |
---|---|
Weight | 826 g |
Dimensions | 210 x 121 x 60 mm (LxWxH) |
Operating temperature | -20 to +50 °C |
Protection class | IP54 |
System requirements | requires iOS 12.0 or newer; requires Android 6.0 or newer; requires mobile end device with Bluetooth 4.0 |
Product colour | Black |
Auto-off | 10 min* |
Battery type | 4 x type AA batteries |
Battery life | 250 h with no illumination, no Bluetooth®; 100 h with illumination and Bluetooth® |
Data transfer | Bluetooth® |
Radio range | 150 m |
Refrigerants in instrument | R407H; R23; R290; R1234yf; R442A; R134a; R123; R452B; R438A; R421A; R453a; R401B; R1233zd; R410A; R407A; R407C; R452A; R401A; R422C; R427A; R422B; R424A; R125; R414B; R404A; R408A; R448A; R422D; R12; R114; R421B; R449A; R409A; R420A; R444B; R32; R454A; R124; R402A; R450A; R407F; R416A; R13; R437A; R1234ze; R454B; R402B; R22; R434A; R454C; R455A; R458A; R500; R502; R503; R507; R513A; R600a; R718 (H₂O); R744 (CO₂) |
Refrigerants update via App | R11; FX80; I12A; R1150; R1270; R13B1; R14; R142B; R152A; R161; R170; R227; R236fa; R245fa; R401C; R406A; R407B; R407D; R41; R411A; R412A; R413A; R417A; R417B; R417C; R422A; R426A; R508A; R508B; R600; RIS89; SP22 |
Storage temperature | -20 to +60 °C |
* when not connected via Bluetooth
Temperature | |
---|---|
Measuring range | -50 to +150 °C |
Accuracy | ±0.5 °C |
Resolution | 0.1 °C |
Probe connection | 2 x plug-in (NTC) |
Pressure measurement | |
---|---|
Measuring range | -1 to 60 bar |
Accuracy | ±0.5 % fs |
Resolution | 0.01 bar |
Probe connection | 3 x 7/16″ – UNF |
Overload rel. (high pressure) | 65 bar |
General technical data | |
---|---|
System requirements | requires iOS 11.0 or newer; requires Android 6.0 or newer; requires mobile end device with Bluetooth 4.0 |